Effect of the Axial Heat Conduction in Parallel Flow Rectangular Microchannel Heat Exchanger
DOI:
https://doi.org/10.31663/utjes.v4i1.176Keywords:
Micro channel, heat exchanger, parallel flow, numerical solution, axial heat conduction and effectivenessAbstract
The axial heat conduction in parallel flow microchannel heat exchanger with rectangular ducts was numerically investigated, for laminar, 3-D, incompressible, and steady state flow of water. The governing equations, continuity, Navier-Stokes equations (momentum equations), and the energy equations for the hot and cold fluids were solved by using SIMPLE algorithm with finite volume method and FORTRAN code to obtain the temperature distribution for the two fluids and the separating wall between them. The results play an important role of the axial heat conduction on the effectiveness in parallel flow microchannel heat exchanger and the factors affecting the axial heat conduction are; Reynolds number Re, thermal conductivity ratio , aspect ratio ? and channel volume. Increasing of Re, , ? and channel volume each separately leads to increase the axial heat conduction and vice versaDownloads
Published
2013-04-01
Issue
Section
Articles
License
Copyright (c) 2013 The Author(s), under exclusive license to the University of Thi-Qar
This work is licensed under a Creative Commons Attribution 4.0 International License.
How to Cite
Effect of the Axial Heat Conduction in Parallel Flow Rectangular Microchannel Heat Exchanger . (2013). University of Thi-Qar Journal for Engineering Sciences, 4(1), 113-137. https://doi.org/10.31663/utjes.v4i1.176